Power Supply:DC 9V (Alkaline dry battery LR14 1.5V 6 PCS, continuous standby for 300 hours ) ( Not included )
Tester Dimension:280mm(L)×260mm(W)×160mm(H)
Weight:1443g
Measuring Method:Earth ground resistance: rated current change-pole method, measurement current 3mA Max,820Hz; Earth Voltage: average value rectification
Measuring Times:Earth voltage : 3 times/second; Earth resistance: 5 seconds/time
Measuring Rate:Over 5000 times (20Ω range measuring 10Ω for one time and repeat after 25 seconds)
Data Storage:400 sets, flash "FULL" symbol to indicate storage is full
Data Hold:Data hold function:"HOLD" symbol display
Data Read:Data read function: "READ" symbol display
Overflow Display:Exceeding measuring range overflow function: "OL" symbol display
Circuit Voltage:Measuring earth voltage : AC 600V MAX
Auxiliary Earth Rod:2 PCS: Φ10mm×150mm
Testing Wires:Five wires: each for Red 20m, yellow 10m, green 5m, red 1.6m, green 1.6m
Interface:USB interface,software supervision, storage data can be uploaded to computer, saved and printed;data transmission line length:1.5m
Wire Resistance Verification:Avoid errors caused by the test line not fully inserted into the instrument interface or poor contact or the user replaces the lengthened test line, ensure grounding resistance measurement more accurate
Alarm Function:Measuring value exceeds alarm setting value, will "Toot-toot-toot" alarm hint
Auto Power-off:15 Minutes after power on, will outage and automatic power off
Battery Voltage:While battery voltage decreases to around 7.8V, will display battery voltage low symbol and reminding to replace the battery