Ground Tester, ETCR2800N Built-in Non-Contact Ground Resistance Tester Meter For Online Monitoring Earth Down Lead Connection Status,Safer and Faster

Imported from USA | Ships in 10 working days

5% instant discount on non COD

1

₹ 48600/-

The price at cart2india.com is inclusive of custom duties, GST, freight forwarding and other charges.

Free Shipping across India. Powered by BlueDart

Product Information


Specification
Brand : LJIA
BulletPoint : Built-in Non-Contact Grounding Resistance Online Detector built for online monitoring grounding down lead connection status, return circuit grounding resistance and metal return circuit connection resistance well-designed manufactured. on-line testing, non-contact measurement, grounding wire pass through the hole, real time on-line testing. Detector provides RS232 and RS485 signal interface, provides standard MODBUS-RTU communication protocol.
BulletPoint1 : Model Number: ETCR3000
BulletPoint2 : Measuring Range: 0.01Ω~2000Ω
BulletPoint3 : Testing Voltage: 0~600V
BulletPoint4 : Accuracy Class: 0.01Ω,1V
BulletPoint5 : Operating Temperature: -10°c~40°c;below 80%rh
Color : One Color
ExternallyAssignedProductIdentifier : 9454352903907
ItemName : Ground Tester, ETCR2800N Built-in Non-Contact Ground Resistance Tester Meter For Online Monitoring Earth Down Lead Connection Status,Safer and Faster
ItemPackageDimensions_Height : 1 centimeters
ItemPackageDimensions_Length : 3 centimeters
ItemPackageDimensions_Width : 2 centimeters
ItemPackageQuantity : 1
ItemTypeKeyword : ground-resistance-meters
Manufacturer : LJIA
Material : abs
ModelName : ETCR2800N
ModelNumber : ETCR2800N
NumberOfItems : 1
PartNumber : ETCR2800N
ProductDescription : Range:0.01~200 ohm; Resolution:0.001Ω
Output range:0.00Ω~200Ω
Accuracy:±2%rdg±3dgt(20℃±5℃,below 70%RH)
Power:6VDC~9VDC,50mA Max.
Weight:About 680g
Dimension:110mm×80mm×55mm
PCBSize:166mm×56mm×20mm
Ground wire perforation size:66mm×36mm
Connection line:1pcs/m (5-core cable)
Single measurement time:About 0.5 seconds
PCB interface:J1: signal output, power input interface J2: sensor and PCB connector

J1
P+: Power input is positive R+: Signal output is positive
P-: power input ground R-: signal output negative
GND: Signal ground, shorted to the power input ground (P-)

J2
I+, I-current coil interface ; U+, U-voltage coil interface; GND: Common ground

Communication Method:RS232, RS485 or MODBUS-RTU communication protocol
Overflow Indication:When the displayed value is over than 200Ω, the communication sends the “OLΩ” command.
<;40A/m
<;1V/m
Installation:Ground thread through the sensor center hole
Installation Requirements:The circuit board needs to be placed in other protective boxes to avoid rain and water immersion installation.
Power Supply:External power supply
Ground Interference Current:Should be avoided
Shift:automatic shifting
Accessories:Sensor: 1 piece; PCB module: 1 piece; connecting line: 1 piece
ProductSiteLaunchDate : 2025-03-25T03:42:04.055Z
Size : One Size
UnitCount : 1
UnspscCode : 41113600

Questions & Answers

Have a question? Ask experts

?
No question found

Ratings & Review

Rating Breakdown (average)

5*
0
4*
0
3*
0
2*
0
1*
0

No reviews found.